Giganet  RT series is small capacity UPS. The output factor is 0.9, and the power range is from 1kVA to 3kVA. Deployment is very flexible, tower and rack-mounted can be configured according to customer's requirement. When UPS is on battery mode, it can shut down unnecessary load and extend the backup time of the critical load.


  • True double-conversion
  • The rack-mounted and floor-standing tower can be convertible
  • Patented Mimic LCD of which content can be rotated according to the type of deployment
  • Digital control guarantees high reliability
  • Output receptacle control for non-critical load shedding capability
  • ECO mode operation for energy saving
  • Emergency power-off function(EPO)
  • Generator compatible
  • Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)
  • The bypass can be used when UPS is off(Set in LCD)
  • Cold start

Features

Nominal Voltage: 08/ 220/230/240Vac(L+N+PE)
Operating Voltage Range: 110~300Vac @(0~60%) Load;120~300Vac @(60~70%)Load, 140~300Vac @(70~80%)Load;160~300Vac @(80~100%)Load
Operating Frequency Range: 50Hz:45~55Hz,60Hz: 55-65Hz Auto Sensing
Power Factor: > 0.85@25%Load;>0.95 @50%Load;>0.97@75%Load;>0.99 @ Nominal voltage& 100%Load
Output Voltage: 208/220/230/240Vac:230Vac(Default)
Power Factor: 0.9
Voltage Regulation: ±1%
Wave form: Pure Sinewave
Transfer time: Utility to Battery : 0ms; Utility to Bypass: 4ms(Typical)

Videos